          英捷思Y500 变频器系统运行过程中发生故障,变频器立即会保护电机停止输出,同时变频器故障继 电器接点动作。变频器面板会显示故障代码,故障代码对应的故障类型和常见解决方法详 见下表。
     英捷思Y500变频器加速过电流Err02解决办法:

    故障原因排查
    1、变频器输出回路存在接地或短路
    2、控制方式为矢量且没有进行参数辨识
    3、加速时间太短
    4、手动转矩提升或V/P曲线不合适
    5、电压偏低
    6、对正在旋转的电机进行启动7、加速过程中突加负载
    8、变频器选型偏小

    故障处理对策
    1、排除外围故障
    2、进行电机参数辨识3、增大加速时间
    4、调整手动提升转知司v/P 出l线
    5、将电压调至正常范围
    6、选择转速追踪启动或等电机停止后再启动
    7、取消突加负载
    8、选用功率等级更大的变频器
     
     

  • 英捷思Y500变频器加速过电流解决办法
  • 联系我们

    CONTACT US

    联系人:张经理

    手机:13389282290

    电话:029-81616045

    邮箱:426184036@qq.com

    地址:陕西自贸区西安国际港务区华南城