    SVG断路器合闸不成功,主控屏允许合闸继电器指示灯未亮;
    可能原因:

    1. SVG主控屏站控装置是否运|行正常;
    2、站控通讯图中主控屏各单元与站控间通讯状态是否正常;
    3、SVG主控屏转换开关是否处于“自检”位置;SVG退出运行断路器断开后,断路器再次合闸的时间间隔小于5分钟。
    解决办法:

    1、重启SVG站控装置;
    2、检耷主挖屏各单元与站控间通讯线是否接插牢固;
    3、主控屏转换开关打到“自检”位置;
    4、等断路器再次合闸时间大于5分钟或重启SVG站控装置;
     
     
     

  • SVG断路器合闸不成功故障